Ultramar Water · Fouling Resistant
FR-8040-400 (34)-ULTRAMAR-WATER
FR-8040-400(34) fouling resistant reverse osmosis membrane The FR-8040-400(34) is an 8-inch spiral wound fouling resistant reverse osmosis membrane, specifically designed for water treatment applications prone to biological and organic fouling. Thanks to a special surface treatment that makes it more hydrophilic, it allows effective cleaning and renewal of the active surface, extending its service life […]
- Diameter
- 8″
- Format
- 8040
FR-8040-400(34) fouling resistant reverse osmosis membrane
The FR-8040-400(34) is an 8-inch spiral wound fouling resistant reverse osmosis membrane, specifically designed for water treatment applications prone to biological and organic fouling. Thanks to a special surface treatment that makes it more hydrophilic, it allows effective cleaning and renewal of the active surface, extending its service life under difficult water conditions. Key operational data includes a permeate flow of 10,500 GPD (40 m³/day), an active membrane area of 400 ft² (37 m²), and a stabilized salt rejection of 99.6%.
Specifications
| Model | Permeate Flow GPD (m³/day) | Active Membrane Area ft² (m²) | Stabilized Salt Rejection | Minimum Salt Rejection | Feed Spacer mil (mm) | Test Conditions |
|---|---|---|---|---|---|---|
| FR-8040-400(34) | 10,500 (40) | 400 (37) | 99.6% | 99.4% | 34 (0.85) | 225 psi / 2,000 ppm NaCl |
Dimensions
| Model | A | B | C |
|---|---|---|---|
| FR-8040-400(34) | 40.0 (1016) | 1.125 (29) | 7.9 (201) |
Operating limits for design
| Maximum Operating Temperature | 45°C (113°F) |
| Maximum Operating Pressure | 600 psi (41 bar) |
| Maximum Pressure Drop (single element) | 15 psi (1.0 bar) |
| pH Range for Continuous Operation | 2–11 |
| pH Range for Cleaning | 1.2–12 |
| Chlorine Tolerance | < 0.1 ppm |
| Maximum Feed SDI | 5 |
Important operation notes
- Discard the permeate produced during the first hour of use.
- Keep elements moist at all times after initial wetting.
- During prolonged shutdowns, store elements in a preservative solution to prevent biological growth, and rinse it out before use.
- The OEM is responsible for the effects of incompatible chemicals and lubricants on the elements.
- Failure to follow these operating limits voids the limited warranty.
Private label and custom versions
The FR-8040-400(34) is available under your brand. Contact our team for volumes, labeling and custom specifications.
Need this membrane in your system?
We can adapt it to your plant, label it with your brand and support you through installation.
Similar membranes