Ultramar Water · Ultra Low Pressure
ULP-8040-400-HR-34-ULTRAMAR-WATER
ULP-8040-400-HR (34) Brackish Water Membrane The ULP-8040-400-HR (34) is an 8-inch spiral wound membrane element designed for brackish water treatment. Its low-pressure, high-productivity design makes it suitable for applications requiring efficient water treatment under low or ultra-low pressure conditions. With a permeate flow of 10,800 GPD (41 m³/day), an active membrane area of 400 ft² […]
- Diameter
- 8″
- Format
- 8040
ULP-8040-400-HR (34) Brackish Water Membrane
The ULP-8040-400-HR (34) is an 8-inch spiral wound membrane element designed for brackish water treatment. Its low-pressure, high-productivity design makes it suitable for applications requiring efficient water treatment under low or ultra-low pressure conditions.
With a permeate flow of 10,800 GPD (41 m³/day), an active membrane area of 400 ft² (37 m²), and a stabilized salt rejection of 99.4%, this element can be considered for water treatment systems designed by OEMs, plant builders and industrial water treatment professionals.
Specifications
| Model | Permeate Flow GPD (m³/day) | Active Membrane Area ft² (m²) | Stabilized Salt Rejection | Minimum Salt Rejection | Feed Spacer mil (mm) | Test Conditions |
|---|---|---|---|---|---|---|
| ULP-8040-400-HR (34) | 10,800 (41) | 400 (37) | 99.4% | 99.2% | 34 (0.85) | 150 psi / 2,000 ppm NaCl |
Dimensions
| Model | A | B | C |
|---|---|---|---|
| ULP-8040-400-HR (34) | 40.0 (1016) | 1.125 (29) | 7.9 (201) |
Operating limits for design
| Maximum Operating Temperature | 45°C (113°F) |
| Maximum Operating Pressure | 600 psi (41 bar) |
| Maximum Pressure Drop (single element) | 15 psi (1.0 bar) |
| pH Range for Continuous Operation | 2–11 |
| pH Range for Cleaning | 2–12 |
| Chlorine Tolerance | < 0.1 ppm |
| Maximum Feed SDI | 5 |
Important operation notes
- Discard the permeate produced during the first hour of use.
- Keep elements moist at all times after initial wetting.
- During prolonged shutdowns, store elements in a preservative solution to prevent biological growth, and rinse it out before use.
- The OEM is responsible for the effects of incompatible chemicals and lubricants on the elements.
- Failure to follow these operating limits voids the limited warranty.
Private label and custom versions
Ultramar Water supports OEMs and water treatment system builders in identifying membrane solutions for their applications. Contact our team to discuss your project requirements and explore available supply options.
Contact Ultramar Water to request further information.
Need this membrane in your system?
We can adapt it to your plant, label it with your brand and support you through installation.
Similar membranes